Flygt leakage sensor FLS10 6630400
Technical Specifications
- Part Number: 663 04 00
- Operating Principle: Current-sensing float switch that changes circuit resistance upon liquid detection
- Electrical Characteristics:
- Supply Voltage: 12 V DC
- Non-alarm Resistance: ~1,200 Ω (10 mA current)
- Alarm Resistance: ~430 Ω (28 mA current)
- Physical Properties: Stainless steel and nitrile rubber construction; dimensions 44mm length × 22mm diameter with M12×1 thread
- Temperature Rating: Maximum 90°C continuous duty
Application Range
Specifically engineered for these pump models introduced after 2000:
- 3153 series
- 3171 series
- 3202 series
- 3301 series
Functionality & Integration
The FLS10 works in conjunction with the MiniCAS II supervision relay, which monitors current levels and triggers leakage alarms when resistance drops below the threshold. Unlike stator-housing sensors (FLS), the FLS10 detects intrusion in the inspection chamber—a less critical zone that typically triggers alarms without automatic pump shutdown, allowing operators to assess the situation. For explosion-proof installations, it's approved for use with thermal switches in Ex-certified pumps.
Installation & Testing
The sensor connects via two-wire, polarity-independent leads to the MiniCAS II relay. Testing can be performed with a standard ohmmeter—resistance should read approximately 1,200 Ω in dry conditions and drop to ~430 Ω when activated. Never apply more than 14 V DC to avoid sensor damage.